Main range of product C60range Multi 9product name C60product or component type Miniature circuit-breakerdevice short name C60Hdevice application Distributionpoles description 2Pnumber of protected poles 2neutral position Left[In] rated current 6 A at 30 °Cnetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 400...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
25 kA Icu at 125 V DC 2P conforming to EN/IEC 60947-2
30 kA Icu at 230...240 V AC 50/60 Hz conforming to EN/IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hz
230...240 V AC 50/60 Hz
400...415 V AC 50/60 Hzmagnetic tripping limit 5...10 x In[Ics] rated service breaking capacity 15 kA conforming to EN/IEC 60947-2 - 12...440 V AC 50/60 Hz
7.5 kA conforming to EN/IEC 60947-2 - 60 V AC 50/60 Hz
5 kA conforming to EN/IEC 60947-2 AC 50/60 Hzlimitation class 3 conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling ON/OFF indicationmounting mode Clip-onmounting support 35 mm symmetrical DIN railcomb busbar and distribution block compatibility YES9 mm pitches 4height 81 mmwidth 36 mmdepth 73 mmnet weight 0.24 kgmechanical durability 20000 cyclesconnections - terminals Tunnel type terminals16 mm² flexible
Tunnel type terminals25 mm² rigidwire stripping length 14 mmearth-leakage protection Separate blocktropicalisation 2 conforming to IEC 60068-1relative humidity 95 % at 55 °Coperating altitude 2000 mambient air temperature for operation -25…60 °Cambient air temperature for storage -40…70 °C