Selection Guide
M200-V1U Single phase under voltage
M200-V1O Single phase over voltage
M200-V1C Single phase combined voltage
M200-V33U three phase three wire under voltage
M200-V33O three phase three wire over voltage
M200-V33C three phase three wire combined
M200-V34U three phase four wire under voltage
M200-V34O three phase four wire over voltage
M200-V34C three phase four wire combined voltage
Typical Applications
The M200 AC voltage relay provides voltage monitoring and protection in both single and three phase systems.
They are used in applications such as mains failure, regulation of power supplies and to protect voltage sensitive equipment.
Under, over and combined under/over units are available.
The relay operates when the externally adjustable trip point is reached. An external differential control is provided with adjustment 1-15%. The differential ensures that the parameter being measured returns to % set above or below (depending on whether it is under or over unit) the trip point before the relay returns to its original state.
As is common with al/the M200 relays; on over units the relay energizes when the input signal exceeds the trip point.
On under units the relay de-energizes when the input signal goes below the trip point.
A red LED indicates the state of the relay, whilst a green LED indicates the condition of the power supply.
Environment
Working temperature 0 to +60 °C
Functional temperature -25 to +70 °C
Storage temperature -40 to +85 °C
Temperature coefficient 0.03% per °C (300ppm/°C)
Relative humidity 95% non condensing
Class of climate HSE complying with DIN40040-3 complying with VDE/VDI3540
Approvals
U.L. Approval File No E157034
Applied Standards
General IEC144/BS5420/VDE/VDI0435/IEC947/EN60947
Safety EN61010-1 DIN57411/VDE0411 ANSI C37
Surge withstand IEC801/EN55020 ANSI C37-90a
Radio screening RFI degree N complying with VDE0875
EMC Emissions EN61326-1
Immunity EN61326-2
Enclosure
Fixing - Snap on to DIN rail 35 x 7.5 mm complying with DIN-EN50022 BS5584
Mounting - Any position
Enclosure Code - Case IP50/terminals IP30 complying with IEC529 BS5490 DIN40050
Insulation
Test Voltage:
4kV RMS 50Hz 1min. between Input/Case/Auxiliary
Impulse Test:
EMC 5kV transient complying with IEC801/EN55020
HF interference:
EHF 2.5kV 1MHz complying with IEC255-4
Protection:
Class II complying with IEC348
Relay Output
Type: Dual pole change-over.
Material: Silver / Cadmium
Contact resistance: 200mOhm max Typically <50m Ohm
Rating AC: 250V 5A non resistive 1200VA
Rating DC: 125V 1A resistive 120 watts
Electrical life: 1e6 operations at above load
Mechanical life: 5e6 operations at above load
Operating time: approx. 7ms (20ms max)
Dielectric strength:
Between coil and contacts: 5kV RMS 1min
Between open contacts: 1kV RMS 1min
Between adjacent contacts: 1kV RMS 1min
Insulation resistance: 1000MOhm at 500V DC
Operating temperature: -30 to +75 °C
Approval: UL and CSA recognised