Square D

Cat# #NE36600LSG

Electronic Trip Circuit Breaker

1200 Amp Frame

3 Pole

600 Volt

Suitable for Continuous Operation at 100% of Rating if used in an Enclosure 48" x 31" x 14" or larger w/ in of 50 Sq. In. of Ventilation at Top and Bottom

Micrologic Trip Unit:

  • Standard Series B
  • LSIG Functions
  • Ground Fault

Rating Plug:

  • ARP050
  • 50%
  • 1200 Amp Sensor
  • 600 Amp Rating
  • Other percentage rating plugs available.  Contact us if you need a different plug

Interrupting Ratings:

  • 125kA @ 240 Volts AC
  • 100kA @ 480 Volts AC
  •   65kA @ 600 Volts AC

Line Side Lugs

Used


(Loc: I-line Breaker Shelf)